A6140模擬輸出模塊
更改設(shè)置設(shè)置分為六組。
?系統(tǒng)配置
?設(shè)置調(diào)整
?控制增益
?分析
?保護/繼電器
?計量/操作
每個設(shè)置組都有一個相應的工具欄按鈕,可以選擇該按鈕訪問該組設(shè)置。單擊菜單欄上的屏幕,然后從列表中選擇所需的設(shè)置組。訪問設(shè)置組后,單個設(shè)置可以查看和更改組的。
通過在設(shè)置字段中單擊并鍵入新設(shè)置來更改設(shè)置。a的范圍限制雙擊設(shè)置可以查看設(shè)置。完成所有所需設(shè)置更改后在設(shè)置組屏幕上,在查看其他屏幕之前,必須將設(shè)置發(fā)送到DECS-100。
否則,設(shè)置更改將丟失。設(shè)置更改可通過單擊發(fā)送至DECS-100SendToDECS按鈕。還可以通過單擊“通信”將設(shè)置發(fā)送到DECS-100菜單欄,然后單擊發(fā)送到DECS。
發(fā)送和接收設(shè)置
當通信啟用時,DECS-100設(shè)置可通過BESTCOMS發(fā)送或接收。發(fā)送設(shè)置通過單擊SendToDECS按鈕將設(shè)置更改發(fā)送到DECS-100。這導致當前設(shè)置屏幕上顯示的選定設(shè)置將變?yōu)镈ECS-100設(shè)置。設(shè)置可以也可以通過單擊菜單欄上的“通信”并單擊“發(fā)送到”發(fā)送到DECS-100德克斯。此外,輸入新值后,按Enter鍵可發(fā)送設(shè)置。這個每次設(shè)置更改為后,必須單擊SendToDECS按鈕或按下Enter鍵確保將所有設(shè)置發(fā)送到DECS-100。請參閱將設(shè)置保存到DECS-100內(nèi)存有關(guān)刪除操作電源后保留DECS-100設(shè)置的信息。
接收設(shè)置通過單擊GetFromDECS按鈕檢索DECS-100設(shè)置。這將導致當前設(shè)置
顯示在設(shè)置屏幕上的DECS-100。通過單擊菜單欄上的通信并單擊從DECS獲取,也可以從DECS100接收設(shè)置。將設(shè)置保存到DECS-100內(nèi)存
設(shè)置保存在非易失性存儲器(EEPROM)中。在斷電的情況下,以下是設(shè)置
它們在加電時激活。如果設(shè)置被更改并發(fā)送到DECS-100,但未發(fā)送到EEPROM,如果DECS-100操作電源丟失,更改的設(shè)置將丟失。退出BESTCOMS或關(guān)閉時
通信時,會詢問您是否要將設(shè)置保存到EEPROM。這個問題甚至被問到如果未進行設(shè)置更改。
當通信啟用時,通過單擊EEPROM將設(shè)置更改保存到EEPROM
按鈕退出時,還可以通過對話框?qū)⒃O(shè)置保存到EEPROM最佳通信或關(guān)閉通信。
CHANGING SETTINGS
Settings are arranged into six groups.
? System Configuration
? Setting Adjustments
? Control Gain
? Analysis
? Protection/Relay
? Metering/Operation
Each setting group has a corresponding toolbar button that can be selected to access that group of
settings. The six setting groups can also be accessed by clicking Screens on the menu bar and then
selecting the desired setting group from the list. Once a setting group is accessed, the individual settings
of the group can be viewed and changed.
A setting is changed by clicking within the setting field and typing the new setting. The range limits of a
setting can be viewed by double-clicking the setting. Once all desired setting changes have been made
on a setting group screen, the settings must be sent to the DECS-100 before viewing other screens.
Otherwise, the settings changes will be lost. Settings changes can be sent to the DECS-100 by clicking
the SendToDECS button. Settings can also be sent to the DECS-100 by clicking Communications on
the menu bar and clicking Send To DECS. SENDING AND RECEIVING SETTINGS
When communication is enabled, DECS-100 settings can be sent or received through BESTCOMS.
Sending Settings
Settings changes are sent to the DECS-100 by clicking the SendToDECS button. This causes the
selected setting displayed on the current settings screen to become the DECS-100 setting. Settings can
also be sent to the DECS-100 by clicking Communications on the menu bar and clicking Send To
DECS. Additionally, a setting can be sent by pressing the Enter key after the new value is typed in. The
SendToDECS button must be clicked or the Enter key must be pressed after each setting change to
ensure that all settings are sent to the DECS-100. See Saving Settings to DECS-100 Memory for
information about retaining DECS-100 settings after operating power is removed.
Receiving Settings
DECS-100 settings are retrieved by clicking the GetFromDECS button. This causes the current settings
of the DECS-100 to be displayed on the settings screen. Settings can also be received from the DECS100 by clicking Communications on the menu bar and clicking Get From DECS.
Saving Settings to DECS-100 Memory
Settings are saved in nonvolatile memory (EEPROM). In the event of a power loss, these are the settings
that are active at power up. If settings are changed and sent to the DECS-100, but not sent to EEPROM,
the changed settings are lost if DECS-100 operating power is lost. When exiting BESTCOMS or closing
communication, you are asked if you want to save the settings to EEPROM. This question is asked even
if no settings changes were made.
When communication is enabled, setting changes are saved to EEPROM by clicking the EEPROM
button. The opportunity to save settings to EEPROM is also given through a dialog box when exiting