勵(lì)磁機(jī)時(shí)間常數(shù)的可用范圍取決于為發(fā)電機(jī)時(shí)間輸入的值常數(shù)(勵(lì)磁機(jī)時(shí)間常數(shù)的默認(rèn)值是發(fā)電機(jī)時(shí)間常數(shù)除以6。)所選發(fā)電機(jī)時(shí)間常數(shù)值必須在1.00到15.00秒之間,并且在0.05之內(nèi)增量。當(dāng)發(fā)電機(jī)時(shí)間常數(shù)值為1.00時(shí),可用勵(lì)磁機(jī)時(shí)間常數(shù)范圍為以0.01秒的增量從0.03增加到0.50。當(dāng)發(fā)電機(jī)時(shí)間常數(shù)值為15.00時(shí),可用勵(lì)磁機(jī)時(shí)間常數(shù)范圍為0.30至3.00,增量為0.01秒。例如,當(dāng)T'do設(shè)置為2.0秒時(shí),Texc為0.33參數(shù)(輸出數(shù)據(jù))自動(dòng)生成。如果T'do設(shè)置為5.00秒,則Texc為0.83秒。計(jì)算的KP為155.47,KI為138.72,KD為48,Kg為1??梢灾苯訌腜ID列表數(shù)據(jù)中刪除、添加或修改PID參數(shù)。
PID參數(shù)也可以保存到文件(pidlist.dat)中
可以將PID參數(shù)添加到列表中,并調(diào)用以進(jìn)行操作和比較。要添加到列表中,請(qǐng)鍵入發(fā)電機(jī)信息框中的發(fā)電機(jī)名稱(或其他適當(dāng)信息)。選擇發(fā)生器時(shí)間常數(shù)。觀察現(xiàn)場(chǎng)輸出數(shù)據(jù)字段中的PID增益參數(shù)。如果這些獲得參數(shù)適當(dāng)時(shí),單擊“添加到PID列表”按鈕。通過拉動(dòng)檢查新參數(shù)在PID列表中向下(單擊向下箭頭)。新的增益和時(shí)間常數(shù)參數(shù)應(yīng)為:顯示。刪除PID列表記錄PID參數(shù)也可以從列表中刪除。要?jiǎng)h除列表(記錄),請(qǐng)下拉PID列表并選擇記錄或列表,以便顯示增益和時(shí)間常數(shù)參數(shù)。單擊“刪除”“記錄”按鈕,并刪除列出的記錄。從PID列表檢索現(xiàn)有數(shù)據(jù)要檢索現(xiàn)有數(shù)據(jù),請(qǐng)下拉PID列表并選擇記錄或列表,以便顯示并高亮顯示常量參數(shù)。單擊“從列表中獲取”按鈕和列出的記錄輸入和輸出數(shù)據(jù)顯示在框中。設(shè)置文件BESTCOMS軟件使您能夠打印DECS-100設(shè)置列表,將DECS-00設(shè)置保存到文件中,并打開設(shè)置文件并將這些設(shè)置上傳到DECS-100在任何文本編輯軟件中編輯。打印設(shè)置文件DECS-100設(shè)置的打印輸出可用于記錄保存或比較目的。DECS-100通過單擊打印圖標(biāo)或單擊菜單欄上的文件,然后單擊打印來打印設(shè)置。
當(dāng)給出打印命令時(shí),以及對(duì)設(shè)置列表的評(píng)論。每個(gè)條目最多限制為54個(gè)字符。什么時(shí)候可以單擊后,打印對(duì)話框提示您選擇打印機(jī)。選擇打印機(jī)后,報(bào)告將印刷的。
The available range for the exciter time constant depends on the value entered for the generator time
constant. (The default value for the exciter time constant is the generator time constant divided by 6.) The
generator time constant value selected must be in the range of 1.00 to 15.00 seconds and in 0.05
increments. When the generator time constant value is 1.00, the available exciter time constant range is
0.03 to 0.50 in 0.01 second increments. When the generator time constant value is 15.00, the available
exciter time constant range is 0.30 to 3.00 in 0.01 second increments. For example, when T'do is set at 2.0 seconds, Texc is 0.33. After specifying the input values, a set of PID
parameters (output data) is generated automatically. If T'do is set at 5.00 seconds, then Texc is 0.83
seconds. The calculated KP is 155.47, KI is 138.72, KD is 48, and Kg is 1.
PID parameters can be directly removed from, added to, or modified in the PID List Data. PID parameters
may also be saved into a file (pidlist.dat). PID parameters can be added to a list and recalled for operation and comparison. To add to the list, type
a name for the generator (or other appropriate information) in the generator information box. Select the
generator time constant. Observe the PID gain parameters in the Field Output Data fields. If these gain
parameters are appropriate, click the Add to PID List button. Check for the new parameters by pulling
down the PID List (click the down arrow). The new gain and time constant parameters should be
displayed.
Removing a PID List Record
PID parameters can also be removed from the list. To remove a list (record), pull down the PID List and
select the record or list so that the gain and time constant parameters are displayed. Click the Remove
Record button and the listed record is deleted.
Retrieving Existing Data from the PID List
To retrieve existing data, pull down the PID List and select the record or list so that the gain and time
constant parameters are displayed and highlighted. Click the Get from a List button and the listed record
input and output data displays in the boxes. SETTINGS FILES
BESTCOMS software enables you to print a list of DECS-100 settings, save DECS-100 settings to a file,
and open a settings file and upload those settings to a DECS-100. A settings file may also be opened and
edited within any text editing software. Printing Settings Files
A printout of DECS-100 settings can be useful for record keeping or comparison purposes. DECS-100
settings are printed by clicking the print icon or clicking File on the Menu bar and then clicking Print.
When the print command is given, a dialog box provides the opportunity to add a title, unit information,
and comments to the settings list. Each entry is limited to a maximum of 54 characters. When OK is
clicked, a print dialog box prompts you to select a printer. Once the printer is selected, the report is
printed.